Platform on concrete and steel in construction
Fire protection of reinforced concrete structures
Concrete structure and additional reinforcement protected with fire-resistant Promat sheet materials.

Fire protection of reinforced concrete structures.

To ensure the bearing capacity of existing concrete structures, they are sometimes reinforced during renovations using steel strips, bonded (carbon) reinforcement, etc. The question then arises: what in case of fire? Should these reinforcements be fire protected?

Concrete structure that needs to be reinforced because of need for increased load bearing due to building repurposing or because of concrete deterioration.

Why reinforce the concrete?

Strengthening of concrete structures is commonly used in renovations and the need for it usually finds its cause in:

  • Changes in the function and use of the building (change of function, creation of openings, increased load, etc.).
  • Damage and degradation of the concrete structure (mechanical damage, reinforcement corrosion, etc.).
  • A faulty design and/or construction (faulty calculation, faulty placement, etc.).

Various systems exist on the market for reinforcing concrete structures. For example, one can use steel plates that are attached to the existing concrete structures with an epoxy adhesive and/or mechanical anchoring. Here it is sometimes necessary to additionally attach them mechanically. In addition, fiber composite epoxy adhesive systems that are glued to the concrete structure to be reinforced are often used.

Protection with sheet material.

What in case of fire?

An engineering firm can determine, based on the accidental load combination according to the Eurocode, whether the reinforcement strips should contribute to the load-bearing capacity of the concrete element (i.e., they should not dislodge) in case of fire. Indeed, in some cases the reinforcement strips do not need to contribute to the load-bearing capacity in case of fire, but the original concrete element may still need additional protection to absorb the internal forces of the accidental load combination in case of fire. 

Additional steel reinforcement glued and/or mechanically attached to the concrete structure.

We distinguish the following possible cases:

1. The concrete structure is sufficiently fire-resistant
2. The existing concrete structure must be additionally fire protected
3. The reinforcement should be fire protected

The concrete structure is sufficiently fire-resistant

Based on EN 1992-1-2 (Eurocode 2) it can be verified whether the concrete structure is sufficiently fire resistant for a certain time. For this one can use the tabulated values for floors, walls, columns and beams. As a function of the required duration of time, the tables include, on the one hand, minimum concrete thicknesses to meet the compartmentation requirement (separation capacity - EI). On the other hand, a minimum reinforcement axis distance is also imposed to ensure the load-bearing capacity (R). In practice, it will therefore be necessary to check whether the concrete element is sufficiently thick and whether the reinforcement axis distance is sufficiently large to guarantee the good behavior of the concrete structure in case of fire.

The existing concrete structure must be fire protected

If point 1 shows that the real reinforcement axis distance is smaller than included in the tabulated values of EN 1992-1-2, one will have to apply additional fire protection. Among other things, this protection will have to ensure that the reinforcing steel does not heat up too much. To protect the concrete, one can, for example, use sheet materials, fire-resistant paint, spray plaster, etc. The protective material used is tested according to standard EN 13381-3. This will show in what thickness the fire protection material must be applied to compensate for the lack of concrete.

Example:

A unidirectional bearing existing concrete floor with a thickness of 140 mm should achieve fire resistance REI 120. Research shows that the reinforcement axis spacing is only 10 mm. Based on Table 5.8 from EN 1992-1-2, this floor should have a minimum thickness of 120 mm and the reinforcement axis spacing should be at least 40 mm. In this case, the floor is sufficiently thick but the reinforcement axis spacing is not respected. In fact, 30 mm of concrete is too short. This means that the protection, which is applied, must have a minimum equivalent concrete thickness of 30 mm.

The reinforcement strip should be fire protected

If the reinforcement strips also contribute to absorbing the load in the event of fire, they will also need to be fire protected. Here, fastening will play a crucial role. 

Glued and mechanically fastened steel plates

When the concrete structure is reinforced with steel strips that are mechanically fastened and bonded, it may be sufficient in the event of fire that only the steel strip remains mechanically fastened. In that case, the steel strip and its attachment must be fire protected. The protection thickness will then be a function of the profile factor and the critical steel temperature. The critical steel temperature can be calculated or one can use a value in absence from EN 1993-1-2 (Eurocode 3), namely 540°C for beams, 500°C for columns and 350°C for prestressed elements.

Critical steel temperature 

If the bonded reinforcement strips are to perform their function even in the event of fire, it will be necessary to ensure that the temperature of the adhesive does not exceed its temperature resistance (glazing temperature of the adhesive (Tg)). This is usually located between 40°C and 80°C. At higher temperatures, the adhesive will soften and the bond will lose its strength, preventing the transfer of forces to the reinforcement strips. In order to prevent the temperature at the adhesive layer from rising too high in the event of a fire, fire-resistant protection must be provided. Fire-resistant boards are often used for this purpose. 

Although there is no specific standard for testing reinforcement strips, tests according to EN 1363-1 'Fire resistance tests - Part 1: General requirements' and/or the EN 1365 series can nevertheless be used to verify that the interface temperature between the sheet material and the reinforcement strips remains sufficiently low, i.e. below the glass transition temperature at a fire exposure according to the ISO 834 fire curve.   

Heeft u vragen over artikel, project of product?

Neem dan rechtstreeks contact op met FEREB asbl.

Contact opnemen

Stel je vraag over dit artikel, project of product?

"*" indicates required fields

This field is for validation purposes and should be left unchanged.
Adres Grootveldlaan 148
1150 Sint Pieters Woluwe
Belgium
Telefoonnummer +32 (0) 15 41 31 24 E-mailadres [email protected] Website fereb.be

"*" indicates required fields

Send us a message

This field is for validation purposes and should be left unchanged.

Wij gebruiken cookies. Daarmee analyseren we het gebruik van de website en verbeteren we het gebruiksgemak.

Details

Kunnen we je helpen met zoeken?